U - Pipe system
1 pipe system and 2 pipe systems
Figure 38: U-shape pipe system for area protection
Min. distance from TITANUS
to T-piece 4 m
Max. distance from TITANUS
to T-piece 20 m
Max. Branch length
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
40 m
50 m
Max. Overall pipe length per pipe system
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
100 m
120 m
Min. Distance between 2 aspiration apertures (d) 4 m
Max. Distance between 2 aspiration apertures (d) 12 m
Max. number of aspiration apertures (n) per pipe system 14 pcs.