EasyManua.ls Logo

WAGNER TITANUS PRO-SENS - U - Pipe System

WAGNER TITANUS PRO-SENS
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITANUS
PRO·SENS
®
Design
06/13
75
U - Pipe system
1 pipe system and 2 pipe systems
Figure 38: U-shape pipe system for area protection
Min. distance from TITANUS
®
to T-piece 4 m
Max. distance from TITANUS
®
to T-piece 20 m
Max. Branch length
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
40 m
50 m
Max. Overall pipe length per pipe system
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
100 m
120 m
Min. Distance between 2 aspiration apertures (d) 4 m
Max. Distance between 2 aspiration apertures (d) 12 m
Max. number of aspiration apertures (n) per pipe system 14 pcs.
5.3.1.2
Pipe systems
Limit values

Table of Contents