Installation
06/13
127
Installation of the second detector module
Figure 73: Installation of the second detector module
1. Only carry out the following work if the device is current-free.
2. With a slot screwdriver, carefully undo the snap-in closures of the hous-
ing by simultaneously pressing in the clips located on one side. Then
carefully lift the housing lid. Pull the cable from the display board and
remove the lid.
3. Carefully remove the cover from the second air sampling pipe (plastic
self-adhesive cover). If necessary use a screwdriver to assist.
4. Carefully break the closure connecting the second pipe system and the
housing (correct breaking point marked by “II”), again using a screw-
driver if required.
5. Spread both support clamps and place the new detector module be-
tween them. Both clamps must fit tightly against the module and snap in
audibly. Press both support clamps together.
6. Pull the jumper JU4 across to the main 1de1 board (see fig. "Connec-
tions for base board X3, X4 and JU4")
6.7