Technical Data
TITANUS
PRO·SENS
®
50
06/13
type radial
service life of fan (12 V) 43.500 h at 24°C
alarm
fault
ON
TITANUS PRO·SENS
®
TITANUS PRO·SENS
®
2
red alarm display 2 red alarm displays
yellow collective fault
green operation display
connection for
external alarm display
response indicator:
type DJ 1191 / Typ DJ 1192
device connector terminals for wires of
max. 1,5 mm²
cable twisted in pairs,
shielded or non-shielded
cable entries 5 x M 20
2 x M 25
tapered
pipe connectors
1 x for ABS pipe
25 mm and
1x for air return
25 mm
2 x for ABS pipe
25 mm and
1x for air return
25 mm
detector module DM-TP-50 ... to 0,5 % light obscuration/m
detector module DM-TP-10 ... to 0,1 % light obscuration/m
detector module DM-TP-01 ... to 0,015 % light obscuration/m
Pipe system – TITANUS
PRO·SENS
®
Pipe system
TITANUS
PRO·SENS
®
PRO·SENS
®
-SL
TITANUS
PRO·SENS
®
2
PRO·SENS
®
2-SL
max. pipe length
max. number of air sampling points
300 m
32
560 m
64
max. length of air sampling hose
per ceiling feed through
1 m
Temperature range
PVC - pipe
ABS - pipe
-0°C...+60°C
-40°C...+80°C
max. monitoring area 2880 m
2
5760 m
2
Fan
Displays on the device
Connections
Response sensitivit
y
4.2
Pipe system