EasyManua.ls Logo

WAGNER TITANUS PRO-SENS - Page 48

WAGNER TITANUS PRO-SENS
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
TITANUS
PRO·SENS
®
48
06/13
alarm
fault
ON
TITANUS PRO·SENS
®
TITANUS PRO·SENS
®
2
red alarm display 2 red alarm displays
yellow collective fault
green operation display
connection for
external alarm display
response indicator:
type DJ 1191 / type DJ 1192
device connector clamps for
max. 1.5 mm²-strands
cable twisted in pairs,
shielded and unshielded
cable entries 5 x M 20
2 x M 25
conical
pipe connectors
1 x for ABS pipe
25 mm und
1x for air return
25 mm
2 x for ABS pipe
 25 mm und
1x for air return
25 mm
detector module DM-TP-50 ... up to 0,5 % light obscuration/m
detector module DM-TP-10 ... up to 0,1 % light obscuration/m
detector module DM-TP-01 ... up to 0,015 % light obscuration/m
Displays at the device
Connections
Response sensitivit
y

Table of Contents

Related product manuals