Commissioning
TITANUS
PRO·SENS
®
168
06/13
If no fault on the air sampling smoke detection system occurred during the
operational check, the pipe system must be checked.
Check that:
1. the pipe system is firmly connected to the pipe connection of TITA-
NUS
®
.
2. all pipe fittings are glued and the pipe system is air tight. For this pur-
pose, first seal all air sampling points (e.g. with insulating tape). Then
measure the air flow at the opening for the air return.
3. the correct aspiration-reducing film sheets were taped over the air sam-
pling points.
NOTICE
After adjusting the air flow sensors (chapter “Air Flow Sensor Adjustment“)
no further alterations must be made to the pipes.
If later alterations become necessary, the air flow sensor must be re-
adjusted.
To carry out the operational check, optional diagnostic software DIAG 3 can
be used.
Follow these steps:
1. Install the diagnostic software on a laptop or PC (PC with serial inter-
face). Windows 95, 98, ME, 2000, NT and XP are suitable.
2. With the enclosed diagnostic cable TITANUS
®
is connected to the PC
via “Diag.” on the base board.
3. The diagnostic software is started up.
4. The monitor of the PC displays the current data of TITANUS
®
visualized.
NOTICE
For a correct colour interpretation, the monitor and graphic card must be
able to depict more than 256 colours.
After completion of the operations check, commissioning of the device with
the pipe system must be repeated from chapter "Adjustment of Air Flow
Sensor”.
Connection chec