Commissioning Protocol for Air Sampling System Type TITANUS PRO · SENS
®
and TITANUS PRO · SENS
®
2
device number
serial number
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
Commissioning
visual check
(
/ –)
depression [Pa]
sensitivity [%/m]
alarm delay [sec]
fault delay [min]
activating threshold
(small/medium/
large/very large)
fault latched (yes/no)
LOGIC · SENS (yes/no)
adjustment dependent on the air pressure (yes/no)
adjustment independent of the air pressure (yes/no)
height
[m
above sea level]
air pressure [hPa]
temperature [°C]
Fault Blockage
LED flashes
(
/ –)
relay drops out after delay time
(
/ –)
signal transmission to central fire panel
(
/ –)
cause of the fault eliminated, LED off
(
/ –)
relay picks up when thresh. is not reached
(
/ –)
cause of fault eliminated, LED memorized
(
/ –)
relay stays dropped out
(
/ –)
Fault Fracture
LED flashes
(/ –)
relay drops out after delay time
(/ –)
signal transmission to central fire panel
(
/ –)
cause of the fault eliminated, LED off
(
/ –)
relay picks up when thresh. is not reached
(
/ –)
cause of fault eliminated, LED memorized
(
/ –)
relay stays dropped out
(
/ –)
Alarm
LED flashes
(
/ –)
relay drops out after delay time
(
/ –)
signal transmission to central fire panel
(/ –)
LED memorized
(/ –)
relay memorized
(/ –)
issuer: …………………………… signature: …………………………………
key:
O.K.
– not O.K.