Commissioning Protocol for Air Sampling System Type TITANUS PRO · SENS
®
and TITANUS PRO · SENS
®
2
device number
serial number
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
measuring and adjustment values
Commissioning
visual check
depression [Pa]
sensitivity [%/m]
alarm delay [sec]
fault delay [min]
activating threshold
large/very large)
fault latched (yes/no)
LOGIC · SENS (yes/no)
adjustment dependent on the air pressure (yes/no)
adjustment independent of the air pressure (yes/no)
height
above sea level]
air pressure [hPa]
temperature [°C]
Fault Blockage
LED flashes
relay drops out after delay time
signal transmission to central fire panel
cause of the fault eliminated, LED off
relay picks up when thresh. is not reached
cause of fault eliminated, LED memorized
relay stays dropped out
Fault Fracture
LED flashes
relay drops out after delay time
signal transmission to central fire panel
cause of the fault eliminated, LED off
relay picks up when thresh. is not reached
cause of fault eliminated, LED memorized
relay stays dropped out
Alarm
LED flashes
relay drops out after delay time
signal transmission to central fire panel
LED memorized
relay memorized
issuer: …………………………… signature: …………………………………
– not O.K.