Technical Description
TITANUS
PRO·SENS
®
24
06/13
The air flow within TITANUS
®
is automatically adjusted so that commission-
ing is made easier. Initialisation can be made dependent or independent of
the air pressure.
In order to make adjustments to an air flow typical within the pipe network, a
process called Air-Flow-Initialisation is used. This must be carried out for
every device once after installation, after each modification to the pipe de-
sign and after any change of ventilator voltage. Thus, the device determines
and memorises the air flow characteristics of the pipe network.
A pipe system up to a total length of 300 m with a maximum number of 32 air
sampling points can be connected to TITANUS
®
.
Two pipe systems can be connected to TITANUS
®
2. The whole pipe system
then measures 2 x 280 m and has a maximum of 2 x 32 aspiration points.