If TITANUS
®
is used in environments with high humidity condensate can oc-
cur in the air sampling system. In order to collect this condensate the steam
trap is installed at the deepest point of the pipe system before the air filter
and the air sampling smoke detection system. The 45°-elbows permit an op-
timum distance to the wall.
The steam trap can be operated in a temperature range between 0°C and
+50°C. The sinter filter in the steam trap has a pore width of 50 µm and ab-
sorbs also coarse dirt particles.
The steam trap is used in the following areas:
areas with widely varying temperatures (high humidity)
areas with fresh air supply