TITANUS
PRO·SENS
®
Technical Description
06/13
45
To prevent the ignition of explosive mixtures by static discharge, the piping
system must be grounded.
Protection Type Nominal Gap Width Explosion Groups Approval
EG IIA > 0,7 mm IIA BAM*
EG IIB3 > 0,5 mm IIB1 – IIB3 BAM*
EG IIC > 0,2 mm IIC BAM*
* Bundesanstalt für Materialprüfung (Federal German Office of Material Re-
search)
NOTICE
The connection between the air sampling smoke detection system and the
detonation prevention de-vice is a metal pipe. During installation the screw-
joint connections must be sealed air-tight with Synthesol or sealing tape.
NOTICE
The installed pipe system in hazardous areas must be grounded.