Design
TITANUS
PRO·SENS
®
68
06/13
The following modules may optionally be used with the corresponding set-
tings for class B or A:
▪ Module 0.015 % LT/m – with a sensitivity of min. 0.12 % LT/m
▪ Module 0.1 % LT/m – with a sensitivity of min. 0.2 % LT/m
Possible system parameters:
▪ I- pipe system
– ≥ 9 V fan voltage, max. 80 m overall pipe length
▪ U- pipe system
– 6.5 V fan voltage, max. 100 m overall pipe length
– 6.9 V fan voltage, max. 110 m overall pipe length
– ≥ 9 V fan voltage, max. 110 m overall pipe length
▪ M- pipe system
– 6.5 V fan voltage, max. 100 m overall pipe length
– 6.9 V fan voltage, max. 110 m overall pipe length
– ≥ 9 V fan voltage, max. 160 m overall pipe length
▪ Double U- pipe system
– 6.5 V fan voltage, max. 140 m overall pipe length
– 6.9 V fan voltage, max. 140 m overall pipe length
– ≥ 9 V fan voltage, max. 160 m overall pipe length
Results: