110 e!RUNTIME Runtime Environment WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
9.4.3 Analog Temperature Inputs
The analog temperature sensor inputs PT1+ / PT1and PT2+ / PT2are
represented at a resolution of 1 digit per 0.1 °C via the INT data type (16 bit).
Table 51: Process Image Analog Temperature Inputs
Chan-
nel
Pin
Data
Type
Mea-
sured
Value
Value Range
Hex.
Dec.
Bin.
PT1+ /
PT1–
X13.1 /
X13.2
INT
60 °C
350 °C
0xFDA8*
0x0DAC
600
3500
1111.1101.
1010.1000*
0000.1101.
1010.1100
PT2+ /
PT2–
X13.3 /
X13.4
>
350 °C
0x0DAC 3500
0000.1101.
1010.1100
*Temperature values below 0 °C are represented in two's complement binary and
hexadecimal.
9.4.4 Digital Inputs
The digital inputs DI1 … DI8 are represented per channel via the BOOL data
type. In addition, the digital inputs are represented via the BYTE data type.
Table 52: Process Image Digital Inputs
Chan-
nel
Pin
Data
Type
Mea-
sured
Value
Value Range
Hex.
Dec.
Bin.
DI [1
8]
X12 BYTE
0 /
+24 V
DC
0x00
0xFF
0 255
0000.0000
1111.1111
DI1 X12.3
BOOL
TRUE /
FALSE
DI2 X12.4
DI3 X12.5
DI4 X12.6
DI5 X12.7
DI6 X12.8
DI7 X12.9
DI8 X12.10
9.4.5 Digital Outputs
The digital outputs DO1 … DO4 are represented per channel via the BOOL data
type. In addition, the digital outputs are represented via the BYTE data type.