EasyManua.ls Logo

WAGO Compact Controller 100 - Digital Outputs; Analog Inputs; Analog Outputs; Table 27: Technical Data - Digital Outputs

WAGO Compact Controller 100
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 Properties WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
4.3.10 Digital outputs
Table 27: Technical Data Digital Outputs
Number of digital outputs
4
Output voltage
24 VDC
Load types
DC, general use (according to UL
61010-2-201, paragraph 4.4.2.101)
Reverse voltage protection
Yes
Switching frequency (max.)
1 kHz
Output current max., 1 output
0.5 A, short-circuit protected
4.3.11 Analog inputs
Table 28: Technical Data – Analog Inputs
Number of analog inputs
2
Connection types
Single-ended
Input voltage, measurement range
0 … 10 V
Input voltage (max.)
±30 V
Typ. input resistance
> 100 k
Resolution
16 bits
Temperature coefficient
< ±0.01 % / K of full scale value
4.3.12 Analog outputs
Table 29: Technical Data Analog Outputs
Number of analog outputs
2
Output voltage, measurement range
0 … 10 V
Load impedance
> 5 k
Typ. settling time
100 ms
Resolution
12 bit
Measurement error at 25 °C
< ±0.2 % of full scale value
Temperature coefficient
< ±0.005 % / K of full scale value

Table of Contents

Related product manuals