68 Mounting WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
6 Mounting
6.1 Installation Position
The following installation positions are permitted:
Table 41: Installation positions and permitted ambient temperatures
Figure
Installation position
Permitted ambient
temperature
Horizontal
25 … +60 °C
Vertical
25 … +55 °C
Bottom
25 … +50 °C
Use an end stop in the case of vertical mounting!
In the case of vertical assembly, an end stop has to be mounted as an additional
safeguard against slipping.
WAGO order no. 249-116 End stop for DIN 35 rail, 6 mm wide
WAGO order no. 249-117 End stop for DIN 35 rail, 10 mm wide