5-30
Reference Limits: d2
User parameters for frequency reference limits are shown in the following table.
Jump Frequencies: d3
User parameters for jump frequencies are shown in the following table.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
d2-01
Frequency
Reference
Upper Limit
Determines maximum
frequency reference, set as a
percentage of maximum
output frequency (E1-04). If
the frequency reference is
above this value, actual Drive
speed will be limited to this
value. This parameter applies to
all frequency reference sources.
0.0
to
110.0
100.0% No A A A A A 289H
Ref Upper
Limit
d2-02
Frequency
Reference
Lower Limit
Sets the output frequency
lower limit as a percentage of
the maximum output
frequency.
0.0
to
110.0
0.0% No A A A A A 28AH
Ref Lower
Limit
d2-03
Master Speed
Reference
Lower Limit
Set the master speed
reference lower limit as a
percent, taking the max.
output frequency to be 100%.
0.0
to
110.0
0.0% No A A A A A 293H
Ref1 Lower
Limit
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
d3-01
Jump
Frequency 1
This parameter allow
programming of up to three
prohibited frequency
reference points for
eliminating problems with
resonant vibration of the
motor / machine. This feature
does not actually eliminate
the selected frequency values,
but will accelerate and
decelerate the motor through
the prohibited bandwidth.
0.0
to
400.0
0.0Hz No A A A A A 294H
Jump Freq 1
d3-02
Jump
Frequency 2
0.0Hz No A A A A A 295H
Jump Freq 2
d3-03
Jump
Frequency 3
0.0Hz No A A A A A 296H
Jump Freq 3
d3-04
Jump
Frequency
Width
This parameter determines
the width of the deadband
around each selected
prohibited frequency
reference point. A setting of
"1.0" will result in a
deadband of +/- 1.0Hz.
0.0
to
20.0
1.0Hz No A A A A A 297H