EasyManua.ls Logo

YASKAWA G7 Series - Page 304

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-86
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
b1-01
Frequency
Reference
Selection
Selects the frequency reference
input source.
0: Operator - Digital preset speed
U1-01 or d1-01 to d1-17.
1: Terminals - Analog input
terminal A1 (or terminal A2
based on parameter H3-09).
2: Serial Com - Modbus RS-422/
485 terminals R+, R-,
S+, and S-.
3: Option PCB - Option board
connected on 2CN.
4: Pulse Input (Terminal RP)
0 to 4 1 No QQQQQ
Reference
Source
b1-02
Run
Command
Selection
Selects the run command input
source.
0: Operator - RUN and STOP
keys on Digital Operator.
1: Terminals - Contact closure on
terminals S1 or S2.
2: Serial Com - Modbus RS-422/
485 terminals R+, R-,
S+, and S-.
3: Option PCB - Option board
connected on 2CN.
0 to 3 1 No QQQQQ
Run Source
H5-01
Drive Node
Address
Selects Drive station node number
(address) for Modbus terminals
R+, R-, S+, S-. The Drive's power
must be cycled for the setting to
take effect.
0 to 20
*
1F No AAAAA
Serial Comm
Adr
H5-02
Communicati
on Speed
Selection
Selects the baud rate for Modbus
terminals R+, R-, S+ and S-. The
Drive's power must be cycled for
the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4 3 No AAAAA
Serial Baud
Rate
H5-03
Communicati
on Parity
Selection
Selects the communication parity
for Modbus terminals R+, R-, S+
and S-. The Drive's power must be
cycled for the setting to take
effect.
0: No Parity
1: Even Parity
2: Odd Parity
0 to 2 0 No AAAAA
Serial Com
Sel
H5-04
Stopping
Method After
Communicati
on Error
Selects the stopping method when
a communication timeout fault
(CE) is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3 3 No AAAAA
Serial Fault
Sel