6-88
MODBUS communications can perform the following operations regardless of the settings in b1-01 and b1-02.
Monitoring operation status from the PLC
Setting and reading parameters
Resetting errors
Inputting multi-function commands
An OR operation is performed between the multi-function commands input from the PLC and commands
input from multi-function contact input terminals S3 to S7.
Message Format
In MODBUS communications, the master sends commands to the slave, and the slave responds. The message
format is configured for both sending and receiving as shown below, and the length of data packets is changed
by the command (function) contents.
The space between messages must support the following.
Fig 6.56 Message Spacing
Slave Address
Set the Drive address from 0 to 32. If you set 0, commands from the master will be broadcast (i.e., the Drive
will not return responses).
Function Code
The function code specifies commands. There are three function codes, as shown below.
Data
Configure consecutive data by combining the storage register address (test code for a loopback address) and
the data the register contains. The data length changes depending on the command details.
Slave address
Function code
Data
Error check
Function Code
(Hexadecimal)
Function
Command Message Response Message
Min.
(Bytes)
Max.
(Bytes)
Min.
(Bytes)
Max.
(Bytes)
03H Read storage register contents 8 8 7 37
08H Loopback test 8 8 8 8
10H Write multiple storage registers 11 41 8 8
Command message
Response message
Command message
PLC to Inverter PLC to InverterInverter to PLC
Time (Seconds)
24 bits long
H5-06
setting
24 bits long
5 ms min.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals