EasyManua.ls Logo

YASKAWA G7 Series - Page 348

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-130
Multi-function Contact Input Functions (H1-01 to H1-10)
Speed Control (ASR) Gain Adjustment for Vector Control
Use the following procedure to adjust C5-01 and C5-03 with the mechanical system and actual load con-
nected.
Setting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
D
Speed control disable setting for V/f control with PG
OFF: Use speed control V/f control with PG
ON: Do not use speed control for V/f control with PG
NoYesNoNoNo
E
Speed control integral reset
Enables switching between PI and P control for the speed control loop.
No No No Yes Yes
77
Speed control (ASR) proportional gain switch (switching between C5-01 and C5-03)
OFF: Use proportional gain in C5-01
ON: Use proportional gain in C5-03
No No No Yes Yes
At zero-speed, increase C5-01
(ASR P Gain 1) until there is no oscillation.
At zero-speed, decrease C5-02
(ASR I Time 1) until there is no oscillation.
Does oscillation develop when the motor
operates at the maximum normal operating
speed?
Decrease C5-01 (ASR P Gain 1).
Increase C5-02 (ASR I Time 1).
YES
NO
Adjustment completed.
(When there is higher-level position control,
adjust the position loop gain so that
overshooting/undershooting doesn’t occur.)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com