6-140
o2-01
Local/Remote
Key Function
Selection
Determines if the Digital
Operator Local/Remote key is
functional.
0: Disabled
1: Enabled
0 to 1 1 NoAAAAA
Local/Remote
Key
o2-02
STOP Key
Function
Selection
Determines if the STOP key on
the Digital Operator will stop the
Drive when Drive is operating
from external terminals or serial
communication.
0: Disabled
1: Enabled
0 to 1 1 NoAAAAA
Oper STOP
Key
o2-03
User Parameter
Default Value
Allows storing of parameter
settings as a User Initialization
Selection.
0: No Change
1: Set Defaults - Saves current
parameter settings as user
initialization. A1-03 now allows
selecting <1110> for user
initialization and returns o2-03 to
zero.
2: Clear All - Clears the currently
saved user initialization. A1-03
no longer allows selecting <1110>
and returns o2-03 to zero.
0 to 2 0 NoAAAAA
User Defaults
o2-05
Frequency
Reference
Setting Method
Selection
Determines if the Data/Enter key
must be used to input a frequency
reference from the Digital
Operator.
0: Disabled - Data/Enter key must
be pressed to enter a frequency
reference.
1: Enabled - Data/Enter key is not
required. The frequency reference
is adjusted by the up and down
arrow keys on the Digital
Operator without having to press
the data/enter key.
0 to 1 0 NoAAAAA
Operator
M.O.P.
o2-07
Cumulative
Operation Time
Setting
Sets the initial value of the
elapsed operation timer U1-13.
0
to
65535
0 hr No A A A A A
Elapsed Time
Set
o2-10
Cumulative
Cooling Fan
Operation Time
Setting
Sets the initial value of the
heatsink fan operation time
monitor U1-40.
0
to
65535
0 hr No A A A A A
Fan ON Time
Set
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C