EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
2-6
Table 2.1 200-240 V Class Wire Sizes
Drive Model
CIMR-
Terminal Symbol
Terminal
Screws
Clamping
Tor qu e
lb•in(N•m)
Terminal
Block
Acceptable
Wire Range
AWG(mm
2
)
Recommended
Wire Size
AWG
(mm
2
)
Wire Type
G7U20P4
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
18 to 10
(0.82 to 5.5)
14
(2)
Power cables,
e.g., 600 V
vinyl power
cables
G7U20P7
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
18 to 10
(0.82 to 5.5)
14
(2)
G7U21P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
18 to 10
(0.82 to 5.5)
14
(2)
G7U22P2
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
18 to 10
(0.82 to 5.5)
12
(3.5)
G7U23P7
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4
10.6 to 13.2
(1.2 to 1.5)
18 to 10
(0.82 to 5.5)
10
(5.5)
G7U25P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M5
20.4 to 22.1
(2.3 to 2.5)
10 to 6
(5.5 to 14)
8
(8)
G7U27P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M5
20.4 to 22.1
(2.3 to 2.5)
10 to 6
(5.5 to 14)
6
(14)
G7U2011
R/L1, S/L2, T/L3, , 1, 2, U/T1,
V/T2, W/T3
M6
35.2 to 44
(4.0 to 5.0)
8 to 1
(8 to 50)
4
(22)
B1, B2
M5
20.4 to 22.1
(2.3 to 2.5)
12 to 6
(3.5 to 14)
Application
Dependent
M6
35.2 to 44
(4.0 to 5.0)
*3 *3
G7U2015
R/L1, S/L2, T/L3, , 1, 2, U/T1,
V/T2, W/T3
M8
79.2 to 88
(9.0 to 10.0)
8 to 1
(8 to 50)
3
(30)
B1, B2
M5
20.4 to 22.1
(2.3 to 2.5)
12 to 6
(3.5 to 14)
Application
Dependent
M6
35.2 to 44
(4.0 to 5.0)
*3 *3
G7U2018
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M8
79.2 to 88
(9.0 to 10.0)
8 to 1/0
(8 to 60)
3
(30)
3
M6
35.2 to 44
(4.0 to 5.0)
8 to 22
(8 to 4)
Application
Dependent
M8
79.2 to 88
(9.0 to 10.0)
*3 *3
G7U2022
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M8
79.2 to 88
(9.0 to 10.0)
8 to 1/0
(50 to 60)
1
(50)
3
M6
35.2 to 44
(4.0 to 5.0)
8 to 22
(8 to 4)
Application
Dependent
M8
79.2 to 88
(9.0 to 10.0)
*3 *3
G7U2030
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M10
155 to 198
(17.6 to 22.5)
N/A
2/0
(60)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M10
155 to 198
(17.6 to 22.5)
2
(30)
r/ 1, / 2
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C