Protective and Diagnostic Functions
7-11
EF3
(blinking)
Ext Fault
S3
External fault (Input terminal S3)
An external fault was input from a
multi-function input terminal (S3 to
S12).
Reset external fault inputs to the
multi-function inputs.
Remove the cause of the external
fault.
EF4
(blinking)
Ext Fault
S4
External fault (Input terminal S4)
EF5
(blinking)
Ext Fault
S5
External fault (Input terminal S5)
EF6
(blinking)
Ext Fault
S6
External fault (Input terminal S6)
EF7
(blinking)
Ext Fault
S7
External fault (Input terminal S7)
EF8
(blinking)
Ext Fault
S8
External fault (Input terminal S8)
EF9
(blinking)
Ext Fault
S9
External fault (Input terminal S9)
EF10
(blinking)
Ext Fault
S10
External fault (Input terminal S10)
EF11
(blinking)
Ext Fault
S11
External fault (Input terminal S11)
EF12
(blinking)
Ext Fault
S12
External fault (Input terminal S12)
FBL
(blinking)
Feed-
back
Loss
PID Feedback Reference Lost
A PID feedback reference loss was
detected (b5-12 = 2) and the PID feed-
back input was less than b5-13 (PID
feedback loss detection level) for
longer than the time set in b5-14 (PID
feedback loss detection time).
--
Table 7.2 Alarm Displays and Processing (Continued)
Display Meaning Probable causes Corrective Actions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C