2-12
4/0 100
M10 100 - 10
M12 100 - 12
M16 100 - 16
250 / 300MCM 125 / 150
M10 150 - 10
M12 150 - 12
M16 150 - 16
400MCM 200 M12 200 - 12
650MCM 325
M12 x 2 325 - 12
M16 325 - 16
* Wire sizes are based on 75 degrees Celsius copper wire.
** Equivalent connector can be used.
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
x wire resistance (W/km) x wire length (m) x current (A) x 10
-3
Wire Size * Terminal Screw
Ring Tongue (R-Type) Closed-Loop Connectors (Lugs)
JST Corporation Part Numbers **