Parameter List
1
1.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 127
No. Name Range Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
L8-38
Carrier Frequency
Reduction
0 - 2 1
*3 *3 *3 *3
-
L8-40
Carrier Freq
Reduction Off-
Delay
0.00 - 2.00 0.01 s 0.50 0.50 0.50 0.50 -
L8-90
STPo Detection
Level (Low
Speed)
0 - 5000 1 - - - - -
n1-15
PWM Voltage
Offset Calibration
0 - 2 1 1 1 1 1 2
n5-04
Speed Response
Frequency
0.00 - 500.00 0.01 Hz - - - 50.00 50.00
n8-35
Initial Pole
Detection Method
0 - 2 1 - - - - -
n8-51
Pull-in Current @
Acceleration
0 - 200 1% - - - - -
o1-03
Frequency
Display Unit
Selection
0 - 3 1 0 0 0 0 0
o1-04
V/f Pattern
Display Unit
0 - 1 1 - - - 0 0
*1 Depends on the setting of o2-04 [Drive Model (KVA) Selection].
*2 Drive models 2211 to 2415 and 4103 to 4720 use these default settings when C6-01 = 1 [Normal / Heavy Duty Selection = Normal Duty
Rating]. Drive models 2257 to 2415, 4140 to 4720 use these default settings when C6-01 = 0 [Heavy Duty Rating].
• A1-02 = 2 [Open Loop Vector]: 2.00
• A1-02 = 3, 4 [Closed Loop Vector, Advanced Open Loop Vector]: 0.05
*3 The default setting changes when C6-01 [Normal / Heavy Duty Selection] changes.
*4 The setting range varies depending on the setting of E5-01 [PM Motor Code Selection] when A1-02 = 5 [Control Method Selection = PM
Open Loop Vector].
*5 The default setting changes when the drive model and setting for E1-03 [V/f Pattern Selection] change.
*6 This is the value for 200 V class drives. Double the value for 400 V class drives.
*7 The maximum value within the setting range is 100.0 when A1-02 = 5 or 7 [Control Method Selection = PM Open Loop Vector or PM
Closed Loop Vector].
*8 The setting range is -100.0 to 100.0 when A1-02 = 5 or 7 [Control Method Selection = PM Open Loop Vector or PM Closed Loop
Vector].
◆ A1-02 = 5 to 8 [Control Method for PM Motors and EZ Vector Control]
No. Name Range Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
b2-01
DC Injection/Zero
SpeedThreshold
0.0 - 10.0 0.1 0.5 Hz 1.0% 0.5% 0.5 Hz
b2-04
DC Inject Braking Time
at Stop
0.00 - 10.00 0.01 s 0.00 0.00 0.00 0.00
b3-01
Speed Search at Start
Selection
0 - 1 1 0 0 - 0
b3-02
SpeedSearch
Deactivation Current
0 - 200 1% - - - -
b3-08
Speed Estimation ACR
P Gain
0.00 - 6.00 0.01 0.50
*1
0.50
*1
- 0.60
*2
b3-09
Speed Estimation ACR
I Time
0.0 - 1000.0 0.1 ms 2.0 4.0 - 10.0
b3-14
Bi-directional Speed
Search
0 - 1 1 - - - 0
b5-15
PID Sleep Function
Start Level
0.0 - 400.0
*3
0.1 0.0 Hz 0.0% 0.0% 0.0 Hz
b6-01
Dwell Reference at
Start
0.0 - 400.0
*3
0.1 0.0 Hz 0.0% 0.0% 0.0 Hz