1.21 Defaults by Drive Model and Duty Rating ND/HD
134 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
No.
*1
Name Unit Default
- Drive Model - 2004 2006 2008 2010
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 62 63 64 65
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
0.75
(0.55)
1
(0.75)
1
(0.75)
1.5
(1.1)
1.5
(1.1)
2
(1.5)
2
(1.5)
3
(2.2)
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor Accel
Time for
Inertia Cal
s 0.178 0.142 0.142 0.142 0.142 0.166 0.166 0.145
L8-02
Overheat
Alarm Level
°C 115 115 115 115 115 115 115 115
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.142 0.142 0.142 0.142 0.166 0.166 0.145
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2012 2018 2021 2030
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 66 67 68 6A
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
3
(2.2)
4
(3.0)
4
(3.0)
5
(3.7)
5
(3.7)
7.5
(5.5)
7.5
(5.5)
10
(7.5)
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient
Value