3.9 Control Circuit Wiring
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 103
■ Output Terminals
Tabl e 3.11 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Table 3.11 Control Circuit Output Terminals
Figure 3.37
Figure 3.36 Connecting a Suppression Diode
■ Serial Communication Terminals
Table 3.12 Control Circuit Terminals: Serial Communications
Type
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Terminals M3 to M6 are available only in CIMR-UB.
<3> Multi-Function Photocoupler Output is available only in CIMR-UA/UD/UT.
<4> Connect a suppression diode as shown in the Figure 3.36 when driving a reactive load such as a relay coil. Make sure the diode rating is greater
than the circuit voltage.
No. Terminal Name (Function) Function (Signal Level) Default Setting Page
Fault Relay Output
MA
N.O. output (Fault)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
276
MB
N.C. output (Fault)
MC
Fault output common
Multi-Function Digital Output
<1>
M1
Multi-function digital output (During run)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
276
M2
M3
<2>
Multi-function digital output (Zero Speed)
M4
<2>
M5
<2>
Multi-function digital output (Speed Agree 1)
M6
<2>
Multi-Function Photocoupler Output
<3>
P1
Photocoupler output 1 (Zero speed)
48 Vdc, 2 to 50 mA
<3>
293
P2
Photocoupler output 2 (Speed agree 1)
PC
Photocoupler output common
Monitor Output
MP
Pulse train output (Output frequency) 32 kHz (max) 293
FM
Analog monitor output 1 (Output frequency)
-10 to +10 Vdc, 0 to +10 Vdc
Resolution: 1/1000
291
AM
Analog monitor output 2 (Output current)
AC
Monitor common 0 V –
Safety Monitor Output
DM+
Safety monitor output
Outputs status of Safe Disable function. Closed when
both Safe Disable channels are closed. Up to +48 Vdc
50 mA.
588
DM-
Safety monitor output
A – External power, 48 V max. C – Coil
B – Suppression diode D – 50 mA or less
Type
<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. For more
information on the termination resistor, see Control I/O Connections on page 110.
No. Signal Name Function (Signal Level)
MEMOBUS/Modbus
Communication
<1>
R+
Communications input (+)
MEMOBUS/Modbus communication: Use a RS-485 or
RS-422 cable to connect the drive.
RS-422/RS-485
MEMOBUS/Modbus communication protocol
115.2 kbps (max.)
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Shield ground 0 V
B
C
D