EasyManua.ls Logo

YASKAWA U1000 Series - TEST RUN WITH LOAD CONNECTED

YASKAWA U1000 Series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
170 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
4.9 Test Run with Load Connected
4.9 Test Run with Load Connected
Test Run with the Load Connected
After performing a no-load test run, connect the motor and proceed to run the motor and load together.
Notes on Connected Machinery
Clear the area around the motor.
The motor should come to a complete stop without problems.
Connect the load and machinery to the motor.
Fasten all installation screws properly. Check that the motor and connected machinery are held in place.
Confirm that the Fast Stop circuit or mechanical safety measures operate correctly.
Be ready to press the STOP button in case of emergency.
Checklist Before Operation
The motor should rotate in the proper direction.
The motor should accelerate and decelerate smoothly.
Operating the Motor under Loaded Conditions
Test run the application similarly to the no-load test procedure when connecting the machinery to the motor.
Watch monitor parameter U1-03 during operation to ensure there is no overcurrent.
If the application permits running the load in the reverse direction, try changing motor direction and the frequency
reference while watching for abnormal motor oscillation or vibration.
Correct any problems that occur with hunting, oscillation, or other control-related issues. Refer to Motor Performance
Fine-Tuning on page 344 for details.