4.6 Application Selection
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 149
Start-Up Programming
& Operation
4
Setting 2: Conveyor Application
Table 4.8 Conveyor: Parameter Settings
Table 4.9 Conveyor: User Parameters (A2-01 to A2-16)
Setting 3: Exhaust Fan Application
Table 4.10 Exhaust Fan: Parameter Settings
Table 4.11 Exhaust Fan: User Parameters (A2-01 to A2-16)
Setting 4: HVAC Fan Application
Table 4.12 HVAC Fan: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Drive Duty Mode Selection 0: Heavy Duty (HD)
No. Parameter Name No. Parameter Name
A1-02 Control Method Selection C1-01 Acceleration Time 1
b1-01 Frequency Reference Selection 1 C1-02 Deceleration Time 1
b1-02 Run Command Selection 1 E2-01 Motor Rated Current
No.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C6-01 Drive Duty Mode Selection 1: Normal Duty (ND)
E1-03 V/f Pattern Selection F: Custom V/f pattern
E1-07 Middle Output Frequency 30.0 Hz
E1-08 Middle Output Frequency Voltage 50.0 V
<1>
L2-01 Momentary Power Loss Operation Selection 1: Enabled
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection 1 E1-07 Middle Output Frequency
b1-02 Run Command Selection 1 E1-08 Middle Output Frequency Voltage
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
b3-01 Speed Search Selection at Start H1-05 Multi-Function Digital Input Terminal S5 Function Selection
C1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function Selection
C1-02 Deceleration Time 1 H1-07 Multi-Function Digital Input Terminal S7 Function Selection
E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts
No.
<1> Max. setting value varies by the drive model selection (o2-04).
Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
b1-17 Run Command at Power Up 1: Run command issued, motor operation start
C6-01 Drive Duty Model Selection 1: Normal Duty (ND)
C6-02 Carrier Frequency Selection 1: 4.0 Hz
<1>
H2-03
CIMR-UA, CIMR-UD, CIMR-UT:Terminal P1-PC Function
Selection (Open-collector)
CIMR-UB:Terminal M3-M4 Function Selection (Relay)
39: Watt Hour Pulse Output
L2-01 Momentary Power Loss Operation Selection
2: CPU Power Active - Drive will restart if power returns prior to control power supply shut
down.
L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
L8-38 Carrier Frequency Reduction Selection 2: Enabled across entire frequency range.
SIEP_C710636_02B_1_0.book 149 ージ 015年11月25日 水曜日 午後4時56