182 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
5.2 b: Application
5.2 b: Application
b1: Operation Mode Selection
b1-01: Frequency Reference Selection 1
Use parameter b1-01 to select the frequency reference source 1 for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light. However, the RUN indicator LED will light in zero speed control when A1-02 is set to 3, 5, or
6.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by using the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or
A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Tabl e 5 .5 for the
input used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Figure 5. 1
Figure 5.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Use the wiring example shown in Figure 5.1 for any other analog input terminals. When using input A2 make sure DIP
switch S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 5.6 to set terminal A2 for current input.
Table 5.6 Analog Input Settings for Frequency Reference Using a Current Signal
No. Parameter Name Setting Range Default
b1-01 Frequency Reference Selection 1 0 to 4 1
Terminal Signal Level
Parameter Settings
Notes
Signal Level Selection Function Selection Gain Bias
A1
0 to 10 Vdc H3-01 = 0
H3-02 = 0
(Frequency Reference Bias)
H3-03 H3-04
-10 to +10 Vdc H3-01 = 1
A2
0 to 10 Vdc H3-09 = 0
H3-10 = 0
(Frequency Reference Bias)
H3-11 H3-12
Make sure to set DIP switch S1 on the
terminal board to “V” for voltage input.
-10 to +10 Vdc H3-09 = 1
A3
0 to 10 Vdc H3-05 = 0
H3-06 = 0
(Frequency Reference Bias)
H3-07 H3-08
-10 to +10 Vdc H3-05 = 1
Terminal Signal Level
Parameter Settings
Notes
Signal Level Selection Function Selection Gain Bias
A2
4 to 20 mA H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-11 H3-12
Make sure to set DIP switch S1 on the
terminal board to “I” for current input.
0 to 20 mA H3-09 = 3
Drive
A1 Analog Input 1
0 to 10 V
AC Analog input common
2 kΩ
V
-V
10.5 V, 20 mA power supply
-10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3
Drive
A1 Analog Input 1
-10 to 10 V
AC Analog input common
4 kΩ
V
-V
10.5 V, 20 mA power supply
-10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3