3.9 Control Circuit Wiring
108 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires
(preparing wire ends as shown in Figure 3.45 and connect the shield to the ground terminal (E [G]) of the drive.
Figure 3. 46
Figure 3.45 Preparing the Ends of Shielded Cables
NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters
when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system
performance.
◆ Module Communications Connector
A connector to connect models CIMR-U40720 to 40930 and the harmonic filter module is called module
connector (CN500).
Be sure to connect the harmonic filter module before turning on or operating the models CIMR-U40720 to 40930.
■
Module Communications Connector Functions
Table 3.16 Module Communications Connector (CN500) Functions
■ Module Communications Connector Location
CIMR-U40720 to 40930
Figure 3. 47
Figure 3.46 Module Communications Connector Location (CIMR-U40720 to 40930)
A – Drive side D –Shield sheath (insulate with tape)
B – Insulation E –Shield
C – Control device side
No. Name Function Page
CN500 Module Communications Connector Connector to communicate information for turning on or operating the models CIMR-U40720 to 40930. 75, 77
E
B
C
D
CN500