EasyManua.ls Logo

YASKAWA U1000 Series - Main Circuit Wiring

YASKAWA U1000 Series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.8 Main Circuit Wiring
Electrical Installation
3
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 89
3.8 Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit
in the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring
practices could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC
bus charge circuit and the control power supply capacitors, and can cause premature drive failures. For the full performance life,
refrain from switching the drive on and off more than once every 30 minutes.
Main Circuit Terminal Functions
CIMR-20028 to 20248, 40011 to 40590
Table 3.2 Main Circuit Terminal Functions (CIMR-20028 to 20248, 40011 to 40590)
CIMR-40720 to 40930
Table 3.3 Main Circuit Terminal Functions (CIMR-40720 to 40930)
Harmonic Filter Module
Table 3.4 Main Circuit Terminal Functions (EUJ7118.)
Voltage Class Three-Phase 200 V Class Three-Phase 400 V Class
Function PageCIMR-U 20028 to 20248 40011 to 40590
Terminal Type
R/L1, S/L2, T/L3 Main circuit power supply input Connects line power to the drive. 71, 73
U/T1, V/T2, W/T3 Drive output Connects to the motor. 71, 73
p1, n1 Momentary power loss recovery unit input
These are the DC voltage terminals that connect to a momentary
power loss recovery unit.
71, 73
100 Ω or less 10 Ω or less Grounding terminal 97
Voltage Class Three-Phase 400 V Class
Function PageCIMR-U 40720 to 40930
Terminal Type
X, Y, Z Main circuit power supply input 1 These are the power supply input terminals that connect to the harmonic filter module.
75, 77
X1, Y1, Z1 Main circuit power supply input 2 These are the power supply input terminals that connect to the harmonic filter module.
r1/ 11, 1/ 21,
t1/ 31
Power Supply Voltage Detection
Input
These terminals are to connect to the harmonic filter module and to detect the power supply voltage
order and voltage levels.
U/T1, V/T2, W/T3 Drive output Connects to the motor.
p1, n1
Momentary power loss recovery
unit input
These are the DC voltage terminals that connect to a momentary power loss recovery unit.
p2, n2 DC voltage output These are the DC voltage terminals that connect to the harmonic filter module. 75, 77
10 Ω or less Grounding terminal 97
Terminal Type Function Page
R/L1, S/L2, T/L3 Main circuit power supply input Connects line power to the harmonic filter module.
75, 77
r1/ 11, 1/ 21,
t1/ 31
Power Supply Voltage Detection
Input
These terminals are to connect to the drive models CIMR-U40720 to 40930 and to detect the
power supply voltage order and voltage levels.
X, Y, Z Filter module output 1
These are the harmonic filter module output terminals that connect to the drive models
CIMR-U40720 to 40930.
X1, Y1, Z1 Filter module output 2
These are the harmonic filter module output terminals that connect to the drive models
CIMR-U40720 to 40930.
p2, n2 DC voltage output
These are the DC voltage output terminals that connect to the drive models CIMR-U40720 to
40930.
10 Ω or less Grounding terminal 97
SIEP_C710636_02B_1_0.book 89 ペー 2015年11月25日 水曜日 午後4時56分