B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
B.6
Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
The following tables show parameters and default settings that change with the drive model selection (o2-04). Parameter
numbers shown in parenthesis are valid for motor 2.
Table B.9 200 V Class Drives Default Settings by Drive Model Selection and ND/HD settings
No. Name Unit Default Settings
Model CIMR-U 20028 20042 20054 20068
C6-01 Drive Duty Selection
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 6A 6B 6D 6E
E2-11 (E4-11) Motor rated Output kW 5.5 7.5 7.5 11 11 15 15 18.5
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 94.75 72.69 72.69 70.44 70.44 63.13 63.13 57.87
C5-17 (C5-37) Motor Inertia
kgm
2
0.026 0.037 0.037 0.053 0.053 0.076 0.076 0.138
C6-02 Carrier Frequency Selection 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 19.6 26.6 26.6 39.7 39.7 53 53 65.8
E2-02 (E4-02) Motor Rated Slip Hz 1.5 1.3 1.3 1.7 1.7 1.6 1.6 1.67
E2-03 (E4-03) Motor No-Load Current A 5.1 8 8 11.2 11.2 15.2 15.2 15.7
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.399 0.288 0.288 0.23 0.23 0.138 0.138 0.101
E2-06 (E4-06) Motor Leakage Inductance % 18.2 15.5 15.5 19.5 19.5 17.2 17.2 20.1
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 172 262 262 245 245 272 272 505
E5-01 Motor Code Selection (for PM Motors) Hex. 120A 120A 120B 120B 120D 120D 120E 120E
L2-02 Momentary Power Loss Ride-Thru Time s 0.7 0.8 0.8 0.9 0.9 1 1 1
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.3 0.3 0.3 0.3 0.3 0.6 0.6 0.6
L2-04 Momentary Power Loss Voltage Recovery Time V 150 150 150 150 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.168 0.175 0.175 0.265 0.265 0.244 0.244 0.317
No. Name Unit Default Settings
Model CIMR-U 20081 20104 20130 20154
C6-01 Drive Duty Selection
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 6F 70 72 73
E2-11 (E4-11) Motor rated Output kW 18.5 22 22 30 30 37 37 45
b3-04 V/f Gain during Speed Search % 100 100 100 80 80 80 80 80
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 57.87 51.79 51.79 46.27 46.27 38.16 38.16 35.78
C5-17 (C5-37) Motor Inertia
kgm
2
0.138 0.165 0.165 0.220 0.220 0.273 0.273 0.333
C6-02 Carrier Frequency Selection 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 65.8 77.2 77.2 105 105 131 131 160
E2-02 (E4-02) Motor Rated Slip Hz 1.67 1.7 1.7 1.8 1.8 1.33 1.33 1.6
E2-03 (E4-03) Motor No-Load Current A 15.7 18.5 18.5 21.9 21.9 38.2 38.2 44
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.101 0.079 0.079 0.064 0.064 0.039 0.039 0.03
E2-06 (E4-06) Motor Leakage Inductance % 20.1 19.5 19.5 20.8 20.8 18.8 18.8 20.2
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 505 538 538 699 699 823 823 852
E5-01 Motor Code Selection (for PM Motors) Hex. 120F 120F 1210 1210 1212 1212 1213 1213
L2-02 Momentary Power Loss Ride-Thru Time s 1 1 1 1.1 1.1 1.1 1.1 1.2
L2-03 Momentary Power Loss Minimum Baseblock Time s 0.6 0.6 0.6 0.6 0.6 0.6 0.6 1
L2-04 Momentary Power Loss Voltage Recovery Time V 150 150 150 150 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.317 0.355 0.355 0.323 0.323 0.32 0.32 0.387