B.5 V/f Pattern Default Values
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 537
Table B.7 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-U20248; CIMR-U40156 to 40930
Table B.8 Default Values of the China Localized Drive: CIMR-UB
No. Units V/f
OLV CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03 − 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), Asia
(Model code: CIMR-UT). For default value of China localized drive (Model code: CIMR-UB), refer to Default Values of the China
Localized Drive: CIMR-UB
on page 537.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
60.0
<44>
60.0
<44>
60.0
<44> <14>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
<14>
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
60.0
<44>
60.0
<44>
60.0
<44> <14>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0
3.0
<44>
3.0
<44>
0.0
<44>
–
E1-08
<18>
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0 12.0 11.0 0.0 –
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5
1.5
<44>
0.5
<44>
0.0
<44> <14>
E1-10
<18>
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0 2.0 0.0 –
Parameter Description
Control Mode (A1-02, E3-01)
V/f, V/f w/PG OLV CLV OLV/PM AOLV/PM CLV/PM
E1-04
<14> Default setting value is dependent on the motor code set to parameter E5-01.
Maximum Output Frequency 50.0 Hz 50.0 Hz 50.0 Hz
<14> <14> <14>
E1-06 Base Frequency 50.0 Hz 50.0 Hz 50.0 Hz
<14> <14> <14>
E1-07 Middle Output Frequency 2.5 Hz 3.0 Hz 0.0 Hz – – –
E1-09 Minimum Output Frequency 1.3 Hz 0.5 Hz 0.0 Hz
<14> <14>
0.0 Hz
E3-04 Motor 2 Max Output Frequency 50.0 Hz 50.0 Hz 50.0 Hz – – –
E3-06 Motor 2 Base Frequency 50.0 Hz 50.0 Hz 50.0 Hz – – –
E3-07 Motor 2 Mid Output Frequency 2.5 Hz 3.0 Hz 0.0 Hz – – –
E3-09 Motor 2 Minimum Output Frequency 1.3 Hz 0.5 Hz 0.0 Hz – – –
SIEP_C710636_02B_1_0.book 537 ページ 2015年11月25日 水曜日 午後4時56分