4.6 Application Selection
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 153
Start-Up Programming
& Operation
4
◆ Setting 7: Traveling Application
Table 4.19 Traveling: Parameters and Settings
Table 4.20 Traveling: User Parameters (A2-01 to A2-16)
No.
<1> Max. setting value varies by the drive model selection (o2-04).
Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-01
Frequency Reference Selection 1
0: Operator
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Drive Duty Mode Selection 0: Heavy Duty (HD)
C6-02 Carrier Frequency Selection 2: 6.0 kHz
<1>
d1-01 Frequency Reference 1 6.0 Hz
d1-02 Frequency Reference 2 30.0 Hz
d1-03 Frequency Reference 3 60.0 Hz
H1-05 Multi-Function Digital Input Terminal S5 Function 3: Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input Terminal S6 Function 4: Multi-Step Speed Reference 2
H2-02
CIMR-UA, CIMR-UD, CIMR-UT:Terminal P1-PC Function Selection
(Open-collector)
CIMR-UB:Terminal M3-M4 Function Selection (Relay)
37: During frequency output
H3-06 Terminal A3 Function Selection 1F: Through mode
L3-04 Stall Prevention Selection during Deceleration 0: Disabled
L8-07 Output Phase Loss Protection Selection 1: Triggered when one output phase is lost
L8-38 Carrier Frequency Reduction Selection 1: Enabled below 6 Hz
L8-41 High Current Alarm Selection 1: Enabled (alarm output)
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection d1-03 Frequency Reference 3
C1-01 Acceleration Time 1 E2-01 Motor Rated Current
C1-02 Deceleration Time 1 H1-05 Multi-Function Digital Input Terminal S5 Function
C6-02 Carrier Frequency Selection H1-06 Multi-Function Digital Input Terminal S6 Function
d1-01 Frequency Reference 1 H2-01 Terminals M1-M2 Function Selection
d1-02 Frequency Reference 2 L1-01 Motor Overload Protection Selection
SIEP_C710636_02B_1_0.book 153 ページ 2015年11月25日 水曜日 午後4時56分