B.4 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 535
◆ E3-01 (Motor 2 Control Mode) Dependent Parameters
Table B.4 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), Asia
(Model code: CIMR-UT). For default value of China localized drive (Model code: CIMR-UB), refer to Default Values of the China
Localized Drive: CIMR-UB
on page 537.
Name Setting Range Resolution
Control Modes (E3-01)
V/f (0) V/f w/PG (1) OLV (2) CLV (3)
C3-21 Motor 2 Slip Compensation Gain 0.0 to 2.5 0.1 0.0 – 1.0 1.0
C3-22 Motor 2 Slip Compensation Primary Delay Time 0 to 10000 1 ms 2000 – 200 –
C5-21 Motor 2 ASR Proportional Gain 1 0.00 to 300.00 0.01 – 0.20 – 20.00
C5-22 Motor 2 ASR Integral Time 1 0.000 to 10.000 0.001 s – 0.200 – 0.500
C5-23 Motor 2 ASR Proportional Gain 2 0.00 to 300.00 0.01 – 0.02 – 20.00
C5-24 Motor 2 ASR Integral Time 2 0.000 to 10.000 0.001 s – 0.050 – 0.500
C5-26 Motor 2 Carrier Frequency Selection 1 to F – 7
<9>
7
<9>
7
<9>
7
<9>
E3-04 Motor 2 Maximum Output Frequency 40.0 to 400.0 0.1 Hz 60.0
<44>
60.0
<44>
60.0
<44>
60.0
<44>
E3-05 Motor 2 Maximum Output Voltage
<18>
0.0 to 255.0 0.1 V 200.0 200.0 200.0 200.0
E3-06 Motor 2 Base Frequency 0.0 to 400.0 0.1 Hz 60.0
<44>
60.0
<44>
60.0
<44>
60.0
<44>
E3-07 Motor 2 Mid Output Frequency 0.0 to 400.0 0.1 Hz 3.0
<44>
3.0
<44>
3.0
<44>
0.0
<44>
E3-08 Motor 2 Mid Output Frequency Voltage
<18>
0.0 to 255.0 0.1 V 15.0 15.0 11.0 0.0
E3-09 Motor 2 Minimum Output Frequency 0.0 to 400.0 0.1 Hz 1.5
<44>
1.5
<44>
0.5
<44>
0.0
<44>
E3-10 Motor 2 Minimum Output Voltage
<18>
0.0 to 255.0 0.1 V 9.0 9.0 2.0 0.0