4.6 Application Selection
150 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Table 4.13 HVAC Fan: User Parameters (A2-01 to A2-16)
Setting 5: Air Compressor Application
Table 4.14 Compressor: Parameter Settings
Table 4.15 Compressor: User Parameters (A2-01 to A2-16):
Setting 6: Hoist Application
Note: 1. Read the instructions listed on page 151 when using Hoist Application Preset
2. Perform Auto-Tuning after selecting the Hoist Application Preset.
Table 4.16 Hoist: Parameters and Settings
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection 1 d2-02 Frequency Reference Lower Limit
b1-02 Run Command Selection 1 E1-03 V/f Pattern Selection
b1-03 Stopping Method Selection E1-04 Maximum Output Frequency
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
C1-01 Acceleration Time 1 H3-11 Terminal A2 Gain Setting
C1-02 Deceleration Time 1 H3-12 Terminal A2 Bias Setting
C6-02 Carrier Frequency Selection L2-01 Momentary Power Loss Operation Selection
d2-01 Frequency Reference Upper Limit o4-12 kWh Monitor Initialization
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C1-01 Acceleration Time 1 5.0 s
C1-02 Deceleration Time 1 5.0 s
C6-01 Drive Duty Model Selection 0: Heavy Duty (HD)
E1-03 V/f Pattern Selection F: Custom V/f pattern
L2-01 Momentary Power Loss Operation Selection 1: Enabled
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection 1 E1-03 V/f Pattern Selection
b1-02 Run Command Selection 1 E1-07 Middle Output Frequency
b1-04 Reverse Operation Selection E1-08 Middle Output Frequency Voltage
C1-01 Acceleration Time 1 E2-01 Motor Rated Current
C1-02 Deceleration Time 1 −−
No.
<1> Max. setting value varies by the drive model selection (o2-04).
Parameter Name Default Setting
A1-02 Control Method Selection 2: Open Loop Vector Control
b1-01 Frequency Reference Selection 1 0: Operator
b6-01 Dwell Reference at Start 3.0 Hz
b6-02 Dwell Time at Start 0.3 s
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Drive Duty Mode Selection 0: Heavy Duty (HD)
C6-02 Carrier Frequency Selection 2: 6.0 kHz
<1>
d1-01 Frequency Reference 1 6.0 Hz
d1-02 Frequency Reference 2 30.0 Hz
d1-03 Frequency Reference 3 60.0 Hz
E1-03 V/f Pattern Selection F: Custom V/f pattern
H2-01 Terminals M1-M2 Function Selection 5: Frequency Detection 2
H2-02
CIMR-UA, CIMR-UD, CIMR-UT:Terminal P1-PC Function Selection
(Open-collector)
CIMR-UB:Terminal M3-M4 Function Selection (Relay)
37: During Frequency Output
H3-06 Terminal A3 Function Selection 1F: Through mode
L2-03 Momentary Power Loss Minimum Baseblock Time 0.3 s
L4-01 Speed Agreement Detection Level 2.0 Hz
L4-02 Speed Agreement Detection Width 0.0 Hz
L6-01 Torque Detection Selection 1 8: UL3, UL4 at speed agree (fault)
L6-02 Torque Detection Level 1 2%
L6-03 Torque Detection Time 1 0.5 s
L8-07 Output Phase Loss Protection Selection 1: Enabled
L8-38 Carrier Frequency Reduction Selection 1: Enabled below 6 Hz
L8-41 High Current Alarm Selection 1: Enabled (alarm is output)