C.5 Drive Operations by MEMOBUS/Modbus
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 565
MEMOBUS/Modbus
Communications
C
C.5 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings.
This section explains the functions that can be used and related parameter settings.
Observing the Drive Operation
A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of
parameter settings (except H5-).
Observe drive status and drive control terminal status from a PLC.
Read and write parameters.
Set and reset faults.
Set multi-function inputs. Inputs settings from the input terminals (S1 to S8) and from MEMOBUS/Modbus
communications are both linked by an OR operation.
Controlling the Drive
To start and stop the drive or set the frequency reference using MEMOBUS/Modbus communications, an external
reference must be selected and the parameters listed in Tab le C.2 must be adjusted accordingly.
Table C.2 Setting Parameters for Drive Control from MEMOBUS/Modbus
Refer to b1-01: Frequency Reference Selection 1 on page 182 and b1-02: Run Command Selection 1 on page 183 for
details on external reference parameter selections. Refer to Setting 2: External reference 1/2 selection on page 267 for
instructions on how to select external reference 1 and 2.
Reference Source Parameter Name Required Setting
External Reference 1
b1-01 Frequency Reference Selection 1 2
b1-02 Run Command Selection 1 2
External Reference 2
b1-15 Frequency Reference Selection 2 2
b1-16 Run Command Selection 2 2
SIEP_C710636_02B_1_0.book 565 ージ 015年11月25日 水曜日 午後4時56