536 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
B.5 V/f Pattern Default Values
B.5 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control).
Table B.5 E1-03 V/f Pattern Settings for Drive Capacity: CIMR-U40011 and 40014
Table B.6 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-U20028 to 20192; CIMR-U40021 to 40124
No. Units V/f
OLV CLV
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), Asia
(Model code: CIMR-UT). For default value of China localized drive (Model code: CIMR-UB), refer to Default Values of the China
Localized Drive: CIMR-UB
on page 537.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
60.0
<44>
60.0
<44>
60.0
<44>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
60.0
<44>
60.0
<44>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0
3.0
<44>
3.0
<44>
E1-08
<18>
V 15.0 15.0 15.0 15.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 15.0 15.0 15.0 15.0 11.0
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5
1.5
<44>
0.5
<44>
E1-10
<18>
V 9.0 9.0 9.0 9.0 8.0 9.0 8.0 9.0 11.0 13.0 11.0 15.0 9.0 9.0 9.0 9.0 2.0
No. Units V/f
OLV CLV
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), Asia
(Model code: CIMR-UT). For default value of China localized drive (Model code: CIMR-UB), refer to Default Values of the China
Localized Drive: CIMR-UB
on page 537.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
60.0
<44>
60.0
<44>
60.0
<44>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
60.0
<44>
60.0
<44>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0
3.0
<44>
3.0
<44>
E1-08
<18>
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 14.0 11.0
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5
1.5
<44>
0.5
<44>
E1-10
<18>
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0 2.0
SIEP_C710636_02B_1_0.book 536 ージ 015年11月25日 水曜日 午後4時56

Table of Contents

Other manuals for YASKAWA U1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA U1000 Series and is the answer not in the manual?

YASKAWA U1000 Series Specifications

General IconGeneral
BrandYASKAWA
ModelU1000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals