456 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
A.3 Three-Phase 400 V Class Drives
A.3 Three-Phase 400 V Class Drives
Table A.3 Power Ratings (Three-Phase 400 V Class)
Item Specification
CIMR-U4 0011 0014 0021 0027 0034 0040 0052 0065 0077 0096 0124 0156
Input/
Output
Rating
Input Current (A)
<1>
HD Rating 8.710131925313647597087113
ND Rating 10 13 19 25 31 36 47 59 70 87 113 142
Rated Input Capacity (kVA)
<2>
HD Rating 8 9 12 17 22 28 33 43 54 64 80 103
ND Rating 9 121722283343546480103130
Rated Output Current
(A)
<3> <4>
HD Rating 9.611142127344052657796124
ND Rating 11 14 21 27 34 40 52 65 77 96 124 156
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency 4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Maximum Output Voltage (V) Proportional to input voltage
<5>
Maximum Output Frequency (Hz) 400 Hz
<6>
Power
Supply
Rated Voltage Rated Frequency
Three-phase (CIMR-U4A/4P) 380 to 500 Vac 50/60 Hz
Three-phase (CIMR-U4E/4W) 380 to 480 Vac 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage
Unbalance
2% or less
Harmonic Current Harmonic Distortion
<5>
5% or less (IEEE519 compliant)
Input Power Factor 0.98% or more (During rated operation)
Item
<1> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<2> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<3> The rated output current of the drive output amps should be equal to or greater than the motor rated current.
<4> Carrier frequency is set to 4 kHz for models CIMR-U40011 to 40414. Carrier frequency is set to 3 kHz for models CIMR-U40477
to 40930. Current derating is required in order to raise the carrier frequency.
<5> If the harmonic current distortion is needed to be 5% or less, the maximum output voltage will be the equivalent to the input voltage × 0.87.
C7-60 (Output Voltage Limit Mode Selection) is needed to be changed from the default setting.
<6> User-adjustable
<7> Use a stand-alone EMC filter with a voltage of 380 to 480 V for models CIMR-U40477 to 40930.
Specification
CIMR-U4 0180 0216 0240 0302 0361 0414 0477 0590 0720 0900 0930
Input/
Output
Rating
Input Current (A)
<1>
HD Rating 142 164 197 218 275 329 377 434 537 655 819
ND Rating 164 197 218 275 329 377 434 537 655 819 846
Rated Input Capacity (kVA)
<2>
HD Rating 130 150 180 200 251 300 344 396 490 598 748
ND Rating 150 180 200 251 300 344 396 490 598 748 773
Rated Output Current
(A)
<3> <4>
HD Rating 156 180 216 240 302 361 414 477 590 720 900
ND Rating 180 216 240 302 361 414 477 590 720 900 930
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency 4 kHz (User adjustable up to 6 kHz. Derating may be required.) 3 kHz
Maximum Output Voltage (V) Proportional to input voltage
<5>
Maximum Output Frequency (Hz) 400 Hz
<6>
Power
Supply
Rated Voltage Rated Frequency
Three-phase (CIMR-U4A/4P) 380 to 500 Vac
<7>
50/60 Hz
Three-phase (CIMR-U4E/4W) 380 to 480 Vac 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage
Unbalance
2% or less
Harmonic Current Harmonic Distortion
<5>
5% or less (IEEE519 compliant)
Input Power Factor 0.98% or more (During rated operation)