5.7 H: Terminal Functions
276 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
H2: Multi-Function Digital Outputs
H2-01 to H2-03: Multi-Function Digital Outputs Function Selection
The drive has three multi-function output terminals. Table 5.40 lists the functions available for theses terminals using
H2-01, H2-02, and H2-03.
Table 5.40 Multi-Function Digital Output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Figure 5. 66
Figure 5.66 During Run Time Chart
No.
Parameter Name
Setting Range Default
CIMR-UA, CIMR-UD, CIMR-UT CIMR-UB
H2-01
Terminal M1-M2 Function Selection (relay) Terminal M1-M2 Function Selection
0 to 192 0: During run
H2-02
Terminal P1-PC Function Selection (open-collector) Terminal M3-M4 Function Selection
0 to 192 1: Zero Speed
H2-03
Terminal P2-PC Function Selection (open-collector) Terminal M5-M6 Function Selection
0 to 192 2: Speed agree 1
Setting Function Page Setting Function Page
0During run 276 1E Restart enabled 283
1 Zero Speed 277 1F Motor overload alarm (oL1) 283
2 Speed agree 1 277 20 Drive overheat pre-alarm (oH) 283
3 User-set speed agree 1 277 22 Mechanical Weakening detection 283
4 Frequency detection 1 278 2F Maintenance period 283
5 Frequency detection 2 278 30 During torque limit 283
6Drive ready 279 31 During speed limit 283
7 During Power Supply Voltage Fault 279 32 During speed limit in Torque Control 283
8 During baseblock (N.O.) 279 33 Zero Servo complete 283
9 Frequency reference source 279 37 During frequency output 283
A Run command source 279 38 Drive enabled 284
B Torque detection 1 (N.O.) 279 39 Power consumption pulse output 284
C Frequency reference loss 280 3A Regenerated power pulse output 284
EFault 280 3C LOCAL/REMOTE Status 284
F Through mode 280 3D During Speed Search 284
10 Minor fault 280 3E PID feedback low 284
11 Fault reset command active 280 3F PID feedback high 284
12 Timer output 280 4C During Fast Stop 284
13 Speed agree 2 280 4D oH pre-alarm time limit 284
14 User-set speed agree 2 281 60 Internal cooling fan alarm 284
15 Frequency detection 3 281 61 Rotor Position Detection Complete 284
16 Frequency detection 4 282 62 Memobus Regs1 (It selects it with H2-07 and H2-08.) 285
17 Torque detection 1 (N.C.)
279
63 Memobus Regs2 (It selects it with H2-09 and H2-10.) 285
18 Torque detection 2 (N.O.) 64 During commercial power operation 285
19 Torque detection 2 (N.C.) 279 90 DriveWorksEZ digital output 1
285
1A During reverse 282 91 DriveWorksEZ digital output 2
1B During baseblock (N.C.) 282 92 DriveWorksEZ digital output 3
1C Motor 2 selection 282 100 to 192 Functions 0 to 92 with inverse output 285
1D During regeneration 283 ––
Status Description
Open Drive is stopped.
Closed A Run command is input or the drive is during deceleration or during DC injection.
ON
ON
OFF
OFF
ONOFF
Run command
Baseblock
command
Output
frequency
During Run