B.3 Parameter Table
484 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
◆ E: Motor Parameters
■ E1: V/f Pattern for Motor 1
d7-02
(2B3H)
Offset Frequency 2
Added to the frequency reference when the digital input “Frequency offset 2” (H1- = 45) is
switched on. A setting of 100% is equal to the drive maximum output current.
Default: 0.0%
Min: -100.0%
Max: 100.0%
243
d7-03
(2B4H)
Offset Frequency 3
Added to the frequency reference when the digital input “Frequency offset 3” (H1- = 46) is
switched on. A setting of 100% is equal to the drive maximum output current.
Default: 0.0%
Min: -100.0%
Max: 100.0%
243
No.(Addr.) Name Description Setting Page
E1-03
(302H)
<3> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).
<14> Default setting value is dependent on the motor code set to E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<21> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<27> When E1-13 (Base Voltage) is set to 0.0, output voltage is controlled with E1-05 (Maximum Voltage) = E1-13. When Auto-Tuning is
performed, E1-05 and E1-13 are automatically set to the same value.
<29> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
<30> The setting value is F in OLV.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA), India (Model code: CIMR-UD), Asia
(Model code: CIMR-UT). For default value of China localized drive (Model code: CIMR-UB), refer to Default Values of the China
Localized Drive: CIMR-UB
on page 537.
V/f Pattern Selection
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern
Default: F
<3>
Min: 0
Max: F
<30>
244
E1-04
(303H)
Maximum Output Frequency
E1-04, E1-06 to E1-13 can only be changed when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the
setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these
rules or an oPE10 fault will occur:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do not
apply.
Note: Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E1-10 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector.
• E1-11, E1-12 and E1-13 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector, Closed Loop Vector.
Default:
<4> <14> <44>
Min: 40.0 Hz
Max: 400.0 Hz
<29>
247
E1-05
(304H)
Maximum Voltage
Default:
<4> <14> <18>
Min: 0.0 V
Max: 255.0 V
<18>
247
E1-06
(305H)
Base Frequency
Default:
<4> <14> <44>
Min: 0.0
Max: E1-04
<29>
247
E1-07
(306H)
Middle Output Frequency
Default:
<4> <44>
Min: 0.0
Max: E1-04
247
E1-08
(307H)
Middle Output Frequency Voltage
Default:
<4> <18>
Min: 0.0 V
Max: 255.0 V
<18>
247
E1-09
(308H)
Minimum Output Frequency
Default:
<4> <14> <44>
Min: 0.0
Max: E1-04
<29>
247
E1-10
(309H)
Minimum Output Frequency
Voltage
Default:
<4> <18>
Min: 0.0 V
Max: 255.0 V
<18>
247
E1-11
(30AH)
<21>
Middle Output Frequency 2
Default: 0.0 Hz
Min: 0.0 Hz
Max: E1-04
247
E1-12
(30BH)
<21>
Middle Output Frequency Voltage
2
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
<18>
247
E1-13
(30CH)
<27>
Base Voltage
Default: 0.0 V
<18>
Min: 0.0 V
Max: 255.0 V
<18>
247
No.(Addr.) Name Description Setting Page
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04