2.2 Mechanical Installation
Mechanical
Installation
2
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 51
harmonic filter module during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause
the harmonic filter module to overheat.
Installation Orientation and Spacing
Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling.
Figure 2.1
Figure 2.1 Correct Installation Orientation
Single Drive Installation
Figure 2.2 and Figure 2.3 show the installation distance required to maintain sufficient space for airflow and wiring.
CIMR-U20028 to 20248, 40011 to 40590
Figure 2.2
Figure 2.2 Correct Installation Spacing
Note: IP20/NEMA 1, UL Type 1 enclosure and IP00 enclosure models require the same amount of space above and below the drive for
installation.
CIMR-U40720 to 40930 and Harmonic Filter Module
Figure 2.3
Figure 2.3 Correct Installation Spacing (CIMR-U40720A and Harmonic Filter Module)
A 50 mm minimum D 120 mm minimum
B 30 mm minimum E Airflow direction
C 200 mm minimum
A 50 mm minimum D 120 mm minimum
B 30 mm minimum E 60 mm minimum
C 200 mm minimum F Airflow direction
A
C
A
BB
D
E
Side Clearance Top/Bottom Clearance
Side Clearance Top/Bottom Clearance
A
A
C
B
B
E
D
F
CIMR-U40720A
Harmonic
Filter Module