3.10 Control I/O Connections
Electrical Installation
3
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 111
Sink/Source Mode, External Power Supply
When using an external voltage source for controlling the digital inputs, set jumper S3 as shown in Figure 3.51. Here,
the inputs can be used for either sinking or sourcing.
Figure 3.52
Figure 3.51 Sink/Source Mode, External Power Supply
Sinking/Sourcing Mode for Digital Inputs (CIMR-UB)
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in Table 3.18 (Default: Sink mode, internal power supply).
Note: Never short terminals SP and SN as doing so will damage the drive.
Table 3.18 Digital Input Sink / Source / External Power Supply Selection (CIMR-UB)
Drive Internal Power Supply
(Terminal SN and SP)
External 24 Vdc Power Supply
Sinking Mode (NPN)
Sourcing Mode (PNP)
Sink Mode (0 V Common) External Power Supply
IP24 V
(24 V)
+24 V
SC
S8
S7
IP24 V
(24 V)
SC
S8
S7
+24 V
Source Mode (+24 V Common) External Power Supply
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24
Vdc
SP
SN
External
24
Vdc
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24 Vdc
SP
SN
External
24 Vdc