128 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
3.16 Wiring Checklist
3.16 Wiring Checklist
No. Item Page
Drive, peripherals, option cards
1 Check drive model number to ensure receipt of correct model. 36
2 Make sure you have the correct peripheral devices. 433
3 Check the option card model number. 433
Installation area and physical setup
4 Ensure that the area surrounding the drive complies with specifications. 50
Power supply voltage, output voltage
5 The voltage from the power supply should be within the input voltage specification range of the drive. 244
6 The voltage rating for the motor should match the drive output specifications. 33
7 Verify that the drive is properly sized to run the motor. 33
8 Power supply voltage of models CIMR-U40477 to 40930 should not exceed 480 V when connecting with recommended EMC filters.
75
77
457
Main circuit wiring
9 Confirm proper branch circuit protection as specified by national and local codes. 70
10 Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3. 79
11
Properly wire the drive and motor together.
The motor lines and drive output terminals U/T1, V/T2, and W/T3 should match in order to produce the desired phase order. If the phase order
is incorrect, the drive will rotate in the opposite direction.
97
12
Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. Wire gauge recommendations based on using 75°C, 600 Vac
vinyl-sheathed wire.
91
13
Use the correct wire gauges for the main circuit. Refer to Main Circuit Wire Gauges and Tightening Torque on page 91. 91
When using comparatively long motor cable, calculate the amount of voltage drop. 91
If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly. 97
14 Properly ground the drive. 97
15
Tightly fasten all terminal screws (control circuit terminals, grounding terminals).
Refer to Main Circuit Wire Gauges and Tightening Torque on page 91.
91
16
Set up overload protection circuits when running multiple motors from a single drive.
Note: Close MC1 through MCn before operating the drive (MC1 through MCn cannot be switched off during run).
17 Verify that ground wiring for models 2E/2W/4E/4W is correct before turning on the EMC filter switch. 119
18 Verify phase advancing capacitors, input noise filters, or ground fault circuit interrupters are NOT installed on the output side of the drive.
19
Properly wire the power lines to terminals X, Y, and Z of models CIMR-U40720 to 4093
0, and terminals X, Y, and Z of the harmonic
filter modu
le.
89
20
Properly wire the power lines to terminals X1, Y1, and Z1 of models CIMR-U40720 to 40930, and terminals X1, Y1, and Z1 of the
harmonic filter module.
21
Properly wire the power lines to terminals p2 and n2 of models CIMR-U40720 to 40930, and terminals p2 and n2 of the harmonic filter
module.
22 The cable between CIMR-U40720 to 40930 and harmonic filter module should not exceed 5 m.
23
The resistance value between the terminals R/L1, S/L2, and T/L3 of the harmonic filter module should exceed 1000 Ω when connected to
models CIMR-U40720 to 40930. If the resistance value does not exceed 1000 Ω, check for main circuit wiring mistakes between the
harmonic filter module and models CIMR-U40720 to 40930.
24 Systems should be interlocked to shut off power to the drive if the drive experiences a fault for models CIMR-U40477 to 40930. 127
Control circuit wiring
25 Use twisted-pair line for all drive control circuit wiring. 99
26
Ground the shields of shielded wiring to the GND terminal.
106
27
If using a 3-wire sequence, properly set parameters for multi-function contact input terminals S1 through S8, and properly wire control
circuits.
3
× wire resistance (Ω/km) × cable length (m) × motor rated current (A) × 10
-3
Motor rated voltage (V) × 0.02 ≥
Thermal
relay
motorPower supply
M1
oL1
oL2
M2
U1000
S3
(external fault)
N.O. input
oL1
oL2
SC
SIEP_C710636_02B_1_0.book 128 ージ 015年11月25日 水曜日 午後4時56