B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 469
Parameter List
B
A2: User Parameters
b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions,
PID control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
No.(Addr.) Name Description Setting Page
A2-01 to
A2-32
(106 to 125H)
<1> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not equal 0.
<2> Default setting value is determined by the Application Preset selected with parameter A1-06.
<69> This setting is the default setting of the Setup Mode parameters. See Table 4.4 for details.
User Parameters 1 to 32
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
Default:
<2> <69>
Min: A1-00
Max: o4-19
181
A2-33
(126H)
User Parameter Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to
A2-17 through A2-32 for quick access.
Default: 1
<1>
Min: 0
Max: 1
181
No.(Addr.) Name Description Setting Page
b1-01
(180H)
Frequency Reference Selection 1
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse train input (terminal RP)
Default: 1
Min: 0
Max: 4
182
b1-02
(181H)
Run Command Selection 1
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Min: 0
Max: 3
183
b1-03
(182H)
Stopping Method Selection
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
Default: 0
Min: 0
Max: 3
<11>
184
b1-04
(183H)
Reverse Operation Selection
0: Reverse enabled.
1: Reverse disabled.
Default: 0
Min: 0
Max: 1
186
b1-05
(184H)
Action Selection below Minimum
Output Frequency
0: Operates according to frequency reference (E1-09 is disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).
Default: 0
Min: 0
Max: 3
187
b1-06
(185H)
Digital Input Reading
0: Input status is read once and processed immediately (for quick response)
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals)
Default: 1
Min: 0
Max: 1
188
b1-07
(186H)
LOCAL/REMOTE Run Selection
0: An external Run command has to be cycled at the new source to be activated.
1: An external Run command at new source is accepted immediately.
Default: 0
Min: 0
Max: 1
188
b1-08
(187H)
Run Command Selection while in
Programming Mode
0: Run command is not accepted while in the Programming Mode.
1: Run command is accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Min: 0
Max: 2
189
b1-14
(1C3H)
Phase Order Selection
0: Standard
1: Switch phase order (reverses the direction of the motor)
Default: 0
Min: 0
Max: 1
189
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV