B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 539
No. Name Unit Default Settings
Model CIMR-U – 20192 20248
C6-01 Drive Duty Selection –
HD ND HD ND
0 1 0 1
o2-04 Drive Model Selection Hex. 74 75
E2-11 (E4-11) Motor rated Output kW 45 55 55 75
b3-04 V/f Gain during Speed Search % 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 35.78 31.35 31.35 23.1
C5-17 (C5-37) Motor Inertia
kgm
2
0.333 0.490 0.490 0.900
C6-02 Carrier Frequency Selection – 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 160 190 190 260
E2-02 (E4-02) Motor Rated Slip Hz 1.6 1.43 1.43 1.39
E2-03 (E4-03) Motor No-Load Current A 44 45.6 45.6 72
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.03 0.022 0.022 0.023
E2-06 (E4-06) Motor Leakage Inductance % 20.2 20.5 20.5 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 852 960 960 1200
E5-01 Motor Code Selection (for PM Motors) Hex. 1214 1214 1215 1215
L2-02 Momentary Power Loss Ride-Thru Time s 1.2 1.3 1.3 1.5
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1 1 1
L2-04 Momentary Power Loss Voltage Recovery Time V 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
n5-02 Motor Acceleration Time s 0.387 0.317 0.317 0.533