5.2 b: Application
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 205
Parameter Details
5
b5-01: PID Function Setting
Enables or disables the PID operation and selects the PID operation mode.
Setting 0: PID disabled
Setting 1: Output frequency = PID output 1
The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
Setting 2: Output frequency = PID output 2
The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.
Setting 3: Output frequency = frequency reference + PID output 1
The PID controller is enabled and the PID output is added to the frequency reference. The PID input is D controlled.
Setting 4: Output frequency = frequency reference + PID output 2
The PID controller is enabled and the PID output is added to the frequency reference. The PID feedback is D controlled.
Setting 5: Mode compatible with setting 1 of similar products from a previous product line
Setting 6: Mode compatible with setting 2 of similar products from a previous product line
Setting 7: Mode compatible with setting 3 of similar products from a previous product line
Setting 8: Mode compatible with setting 4 of similar products from a previous product line
Note: Set the values 5 to 8 instead of 1 to 4 when upgrading the drive from previous Yaskawa drive models such as Varispeed F7.
b5-02: Proportional Gain Setting (P)
Sets the P gain that is applied to the PID input. A large value will tend to reduce the error, but may cause instability
(oscillations) if set too high. A low value may allow too much offset between the setpoint and feedback.
b5-03: Integral Time Setting (I)
Sets the time constant that is used to calculate the integral of the PID input. The smaller the integral time set to b5-03, the
faster the offset will be eliminated. If set too short, it can cause overshoot or oscillation. To turn off the integral time, set
b5-03 = 0.00.
b5-04: Integral Limit Setting
Sets the maximum output possible from the integral block. Set as a percentage of the maximum frequency (E1-04).
Note: On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of
oscillation. To suppress this oscillation, a limit can be applied to the integral output by programming b5-04.
b5-05: Derivative Time (D)
Sets the time the drive predicts the PID input/PID feedback signal. Longer time settings will improve the response but
can cause vibrations. Shorter settings will reduce the overshoot but also reduce the controller responsiveness. D control is
disabled by setting b5-05 to zero seconds.
No. Parameter Name Setting Range Default
b5-01 PID Function Setting 0 to 8 0
No. Name Setting Range Default
b5-02 Proportional Gain Setting (P) 0.00 to 25.00 1.00
No. Name Setting Range Default
b5-03 Integral Time Setting (I) 0.0 to 360.0 s 1.0 s
No. Name Setting Range Default
b5-04 Integral Limit Setting 0.0 to 100.0% 100.0%
No. Name Setting Range Default
b5-05 Derivative Time (D) 0.00 to 10.00 s 0.00 s
SIEP_C710636_02B_1_0.book 205 ージ 015年11月25日 水曜日 午後4時56