EasyManua.ls Logo

YASKAWA U1000 Series - Page 505

YASKAWA U1000 Series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 505
Parameter List
B
H4: Multi-Function Analog Outputs
15 General Torque Limit
10 V = Motor rated torque
291
16 Differential PID Feedback
10 V = 100%
291
1F Through Mode
Select this setting when the terminal is not used or when using the terminal in the pass-through mode.
291
30 to 32 DriveWorksEZ Analog Input 1 to 3
Output is determined by the function selected using DWEZ.
291
No.(Addr.) Name Description Setting Page
H4-01
(41DH)
Multi-Function Analog Output
Terminal FM Monitor Selection
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U-. For example, enter “103”
for U1-03.
Default: 102
Min: 000
Max: 999
291
H4-02
(41EH)
Multi-Function Analog Output
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
Default: 100.0%
Min: -999.9%
Max: 999.9%
291
H4-03
(41FH)
Multi-Function Analog Output
Terminal FM Bias
Sets the bias value added to the terminal FM output signal.
Default: 0.0%
Min: -999.9%
Max: 999.9%
291
H4-04
(420H)
Multi-Function Analog Output
Terminal AM Monitor Selection
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U-. For example, enter “103”
for U1-03.
Default: 103
Min: 000
Max: 999
291
H4-05
(421H)
Multi-Function Analog Output
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
Default: 50.0%
Min: -999.9%
Max: 999.9%
291
H4-06
(422H)
Multi-Function Analog Output
Terminal AM Bias
Sets the bias value added to the terminal AM output signal.
Default: 0.0%
Min: -999.9%
Max: 999.9%
291
H4-07
(423H)
Multi-Function Analog Output
Terminal FM Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
293
H4-08
(424H)
Multi-Function Analog Output
Terminal AM Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
293
H3 Multi-Function Analog Input Settings
Setting Function Description (For when output is 100%) Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 505 ージ 015年11月25日 水曜日 午後4時56