B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 505
■ H4: Multi-Function Analog Outputs
15 General Torque Limit
10 V = Motor rated torque
291
16 Differential PID Feedback
10 V = 100%
291
1F Through Mode
Select this setting when the terminal is not used or when using the terminal in the pass-through mode.
291
30 to 32 DriveWorksEZ Analog Input 1 to 3
Output is determined by the function selected using DWEZ.
291
No.(Addr.) Name Description Setting Page
H4-01
(41DH)
Multi-Function Analog Output
Terminal FM Monitor Selection
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U-. For example, enter “103”
for U1-03.
Default: 102
Min: 000
Max: 999
291
H4-02
(41EH)
Multi-Function Analog Output
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
Default: 100.0%
Min: -999.9%
Max: 999.9%
291
H4-03
(41FH)
Multi-Function Analog Output
Terminal FM Bias
Sets the bias value added to the terminal FM output signal.
Default: 0.0%
Min: -999.9%
Max: 999.9%
291
H4-04
(420H)
Multi-Function Analog Output
Terminal AM Monitor Selection
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U-. For example, enter “103”
for U1-03.
Default: 103
Min: 000
Max: 999
291
H4-05
(421H)
Multi-Function Analog Output
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
Default: 50.0%
Min: -999.9%
Max: 999.9%
291
H4-06
(422H)
Multi-Function Analog Output
Terminal AM Bias
Sets the bias value added to the terminal AM output signal.
Default: 0.0%
Min: -999.9%
Max: 999.9%
291
H4-07
(423H)
Multi-Function Analog Output
Terminal FM Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
293
H4-08
(424H)
Multi-Function Analog Output
Terminal AM Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
293
H3 Multi-Function Analog Input Settings
Setting Function Description (For when output is 100%) Page
OLV/PM AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 505 ページ 2015年11月25日 水曜日 午後4時56分