518 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
o2: Digital Operator Keypad Functions
o3: Copy Function
o4: Maintenance Monitor Settings
o1-10
(520H)
User-Set Display Units Maximum
Va lu e
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Default:
<36>
Min: 1
Max: 60000
332
o1-11
(521H)
User-Set Display Units Decimal
Display
Default:
<36>
Min: 0
Max: 3
332
<10> Default setting is determined by the control mode (A1-02).
<36> Default setting value is determined by the digital operator display selection (o1-03).
No. (Addr.) Name Description Setting Page
o2-01
(505H)
LO/RE (LOCAL/REMOTE) Key
Function Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Min: 0
Max: 1
332
o2-02
(506H)
STOP Key Function Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Min: 0
Max: 1
333
o2-03
(507H)
User Parameter Default Value 0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
Default: 0
Min: 0
Max: 2
333
o2-04
(508H)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board.
Default: Determined by
drive capacity
Min: –
Max: –
333
o2-05
(509H)
Frequency Reference Setting
Method Selection
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using the up and down
arrow keys only.
Default: 0
Min: 0
Max: 1
333
o2-06
(50AH)
Operation Selection when Digital
Operator is Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min: 0
Max: 1
334
o2-07
(527H)
Motor Direction at Power Up when
Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
Default: 0
Min: 0
Max: 1
334
o2-09
(50DH)
Reserved
No. (Addr.) Name Description Setting Page
o3-01
(515H)
Copy Function Selection
0: Copy select
1: INV OP READ (Read parameters from the drive, saving them onto the digital operator.)
2: OP INV WRITE (Copy parameters from the digital operator, writing them to the drive.)
3: OP INV VERIFY (Verify parameter settings on the drive to check if they match the data
saved on the operator.)
To read the drive’ parameter settings into the digital operator, set o3-02 to 1 (to allow reading).
Default: 0
Min: 0
Max: 3
334
o3-02
(516H)
Copy Allowed Selection Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed
Default: 0
Min: 0
Max: 1
335
No. (Addr.) Name Description Setting Page
o4-01
(50BH)
Cumulative Operation Time
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h.
Default: 0
Min: 0
Max: 9999
335
o4-02
(50CH)
Cumulative Operation Time
Selection
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Default: 0
Min: 0
Max: 1
335
o4-03
(50EH)
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Default: 0
Min: 0
Max: 9999
335
o4-05
(51DH)
Capacitor Maintenance Setting
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to check when the
capacitors may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
335
No. (Addr.) Name Description Setting Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes