B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual 531
Parameter List
B
U8: DriveWorksEZ Monitors
U9: Power Monitors
No. (Addr.) Name Description
Analog Output
Level
Unit Page
U8-01 to
U8-10
(1950H to
1959H)
DriveWorksEZ Custom
Monitor 1 to 10
DriveWorksEZ Custom Monitor 1 to 10
10 V: 100% 0.01%
U8-11 to
U8-13
(195AH to
195CH)
DriveWorksEZ Version
Control Monitor 1 to 3
DriveWorksEZ Version Control Monitor 1 to 3
No signal output
available
––
No. (Addr.) Name Description
Analog Output
Level
Unit Page
U9-01
(820H)
Electric Power (GWh)
Shows the total amount of electric power consumed.
No signal output
available
1 GWh
U9-02
(821H)
Electric Power (MWh)
No signal output
available
1 MWh
U9-03
(822H)
Electric Power (kWh)
No signal output
available
1 kWh
U9-04
(823H)
Regenerative Power (GWh)
Shows the total amount of regenerated power.
No signal output
available
1 GWh
U9-05
(824H)
Regenerative Power (MWh)
No signal output
available
1 MWh
U9-06
(825H)
Regenerative Power (kWh)
No signal output
available
1 kWh
U9-07 to
U9-10
(826H to
829H)
Electric Power Rates 1 to 4
These parameters show the electric power rate in Power Unit Price (o4-19) that is calculated
from the total electrical power consumption in U9-01 to U9-03.
U9-10: Digit 1 to digit 3
U9-09: Digit 4 to digit 6
U9-08: Digit 7 to digit 9
U9-07: Digit 10 to digit 12
The values shown in U9-07 to U9-10 are calculated by multiplying U9-01 to U9-03 by the value
set in o4-19.
No signal output
available
––
U9-11 to
U9-14
(82AH to
82DH)
Regenerative Power Rates
1 to 4
These parameters show the regenerative power rate in Power Unit Price (o4-19) that is
calculated from the total electrical power consumption in U9-04 to U9-06.
U9-14: Digit 1 to digit 3
U9-13: Digit 4 to digit 6
U9-12: Digit 7 to digit 9
U9-11: Digit 10 to digit 12
The values shown in U9-11 to U9-14 are calculated by multiplying U9-04 to U9-06 by the value
set in o4-19.
No signal output
available
––
All Modes
All Modes
All Modes
000 000 000 kW
U9-03
U9-02
U9-01
All Modes
000 000 000 kW
U9-06
U9-05
U9-04
All Modes
000 000 000 000
U9-10
U9-09
U9-08
U9-07
All Modes
000 000 000 000
U9-14
U9-13
U9-12
U9-11
SIEP_C710636_02B_1_0.book 531 ージ 015年11月25日 水曜日 午後4時56