B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
542 YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
No. Name Unit Default Settings
Model CIMR-U – 40361 40414 40477 40590
C6-01 Drive Duty Selection –
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. A9 AA AC AD
E2-11 (E4-11) Motor rated Output kW 160 185 185 220 220 260 260 300
b3-04 V/f Gain during Speed Search % 60 60 60 60 60 60 60 60
b3-06 Output Current 1 during Speed Search – 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 30.13 30.57 30.57 27.13 27.13 21.76 21.76 21.76
C5-17 (C5-37) Motor Inertia
kgm
2
3.30 3.60 3.60 4.10 4.10 6.50 6.50 11.00
C6-02Carrier Frequency Selection –11110000
E2-01 (E4-01) Motor Rated Current A 270 310 310 370 370 500 500 500
E2-02 (E4-02) Motor Rated Slip Hz 1.35 1.3 1.3 1.3 1.3 1.25 1.25 1.25
E2-03 (E4-03) Motor No-Load Current A 70 81 81 96 96 130 130 130
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.029 0.025 0.025 0.02 0.02 0.014 0.014 0.014
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 2850 3200 3200 3700 3700 4700 4700 4700
E5-01 Motor Code Selection (for PM Motors) Hex. 124A 124A FFFF FFFF FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 1.8 1.9 1.9 2 2 2.1 2.1 2.1
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1 1 1 1.8 2.0 2.0 2.0
L2-04 Momentary Power Loss Voltage Recovery Time V 300 300 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 30 30 100 100 100 100 100 100
n5-02 Motor Acceleration Time s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
No. Name Unit Default Settings
Model CIMR-U – 40720 40900 40930
C6-01 Drive Duty Selection –
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. AE AF B0
E2-11 (E4-11) Motor rated Output kW 300 375 375 450 450 500
b3-04 V/f Gain during Speed Search % 60 60 60 60 60 60
b3-06 Output Current 1 during Speed Search – 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.8 0.8 0.8 0.8 0.8 0.8
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 21.76 23.84 23.84 21.40 21.40 20.26
C5-17 (C5-37) Motor Inertia
kgm
2
11.00 12.00 12.00 13.00 13.00 14.00
C6-02 Carrier Frequency Selection – 0 0 0 0 0 0
E2-01 (E4-01) Motor Rated Current A 500 650 650 800 800 900
E2-02 (E4-02) Motor Rated Slip Hz 1.25 1.00 1.00 1.00 1.00 0.90
E2-03 (E4-03) Motor No-Load Current A 130 130 130 160 160 180
E2-05 (E4-05) Motor Line to Line Resistance Ω 0.014 0.012 12.000 mΩ 10.000 mΩ 10.000 mΩ 9.000 mΩ
E2-06 (E4-06) Motor Leakage Inductance % 20 20 20 20 20 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 4700 5560 5560 7060 7060 7833
E5-01 Motor Code Selection (for PM Motors) Hex. FFFF FFFF FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 2.1 2.3 2.3 2.8 2.8 3.1
L2-03 Momentary Power Loss Minimum Baseblock Time s 2.0 2.2 2.2 2.6 2.6 3.0
L2-04 Momentary Power Loss Voltage Recovery Time V 300 300 300 300 300 300
L8-02 Overheat Alarm Level °C 135 135 135 135 135 135
L8-35 Installation Method Selection – 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 100 100 100 100 100 100
n5-02 Motor Acceleration Time s 1.392 1.667 1.667 2.000 2.000 2.222
SIEP_C710636_02B_1_0.book 542 ページ 2015年11月25日 水曜日 午後4時56分