Table B.21 200 V, 1450 min
-1
Type YASKAWA SST4 Series IPM Motor
No. Name Unit Default Settings
E5-01
Motor Code Selection (for PM Motors) − 2302 2303 2305 2306 2308 230A 230B 230D
Voltage Class V 200 200 200 200 200 200 200 200
Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated Speed
min
-1
1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0
E5-03 Motor Rated Current (for PM Motors) A 1.77 3.33 5.94 9.48 14.17 20.42 27.92 39.6
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω 3.154 1.835 0.681 0.308 0.405 0.278 0.180 0.098
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH 28.46 19.46 10.00 6.88 8.15 5.77 6.32 3.34
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH 39.29 25.89 15.20 9.25 10.76 8.60 8.80 4.61
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs/rad 268.8 256.9 271.9 260.2 286.8 314.9 300.8 292.3
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/(min
-1
)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia
kgm
2
0.0016 0.0022 0.0081 0.0133 0.0133 0.017 0.027 0.044
n5-02 Motor Acceleration Time s 0.092 0.068 0.125 0.139 0.083 0.070 0.082 0.092
n8-49
d-Axis Current for High Efficiency
Control (for PM Motors) (OLV/PM)
% -7.5 -9.4 -13.9 -10.0 -15.0 -17.9 -22.7 -20.5
No. Name Unit Default Settings
E5-01
Motor Code Selection (for PM Motors) − 230E 230F 2310 2312 2313 2314 2315 2316
Voltage Class V 200 200 200 200 200 200 200 200
Rated Power kW1518223037455575
Rated Speed
min
-1
1450 1450 1450 1450 1450 1450 1450 1450
E5-02 Motor Rated Power (for PM Motors) kW 15.0 18.50 22.00 30.00 37.00 45.00 55.00 75.00
E5-03 Motor Rated Current (for PM Motors) A 54.2 68.3 75.2 102.0 131.3 160.4 191.7 257.3
E5-04 Number of Motor Poles (for PM Motors) – 6 6 6 6 6 6 6 6
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω 0.073 0.055 0.048 0.034 0.023 0.016 0.012 0.007
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH 2.94 2.23 2.08 1.67 1.39 0.94 0.82 0.56
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH 3.65 2.85 2.66 2.04 1.73 1.22 1.06 0.76
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs/rad 305.1 297.6 355.8 355.4 324.0 302.4 337.2 323.4
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/(min
-1
)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia
kgm
2
0.054 0.063 0.113 0.137 0.252 0.304 0.41 0.55
n5-02 Motor Acceleration Time s 0.083 0.079 0.118 0.105 0.157 0.156 0.172 0.169
n8-49
d-Axis Current for High Efficiency
Control (for PM Motors) (OLV/PM)
% -14.6 -16.4 -11.8 -10.5 -14.5 -17.4 -13.9 -17.5
SIEP_C710636_02B_1_0.book 553 ページ 2015年11月25日 水曜日 午後4時56分